Skip Navigation View Sitemap

Indoor cables (halogen-free)

JE-H(St)H Bd Si mtp B2ca / Cca / Dca

JE-H(St)H Bd Si mtp B2ca / Cca / Dca
acc. to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Outer sheath: halogen-free compound; colour: pebble grey RAL 7032 or blue RAL 5015
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22, DIN EN 60332-3-22
  • Smoke density: IEC 61034, DIN EN 61034

JE-HCH Bd Si mtp B2ca / Cca / Dca

JE-HCH Bd Si mtp B2ca / Cca / Dca
acc. to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen: tinned copper wire braid (Ø 0.2 mm)
  • Outer sheath: halogen-free compound; colour: pebble grey RAL 7032 or blue RAL 5015
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22, DIN EN 60332-3-22
  • Smoke density: IEC 61034, DIN EN 61034

JE-LIHCH Bd Si mtp Eca/Dca

JE-LIHCH Bd Si mtp Eca/Dca
acc. to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen: tinned copper wire braid (Ø 0.2 mm)
  • Outer sheath: halogen-free compound; colour: pebble grey RAL 7032 or blue RAL 5015
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22, DIN EN 60332-3-22
  • Smoke density: IEC 61034, DIN EN 61034

JE-LIHCHSH Bd Si mtp Fca

JE-LIHCHSH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Application
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen: tinned copper wire braid (Ø 0.2 mm)
  • Sheath: halogen free compound
  • Armouring: galvanized steel wire braid (Ø 0.24 mm); optical coverage approx. 80 %
  • Outer sheath: halogen-free compound; colour: pebble grey RAL 7032 or blue RAL 5015
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-24, DIN EN 60332-3-24
  • Smoke density: IEC 61034, DIN EN 61034
Back to top